FLYGT Industrial Partner

FPC 100 - Flygt Xylem FPC 100 Single Pump Controller Simple Type: Pump

larger image

Request Quote
For Price
Part Number:
FPC 100
Model Number:
FPC 100
Make:
FLYGT
Lead Time:
Available
Qty In Stock:
Available

Flygt Xylem FPC 100 Single Pump Controller Simple Type: Pump

The FPC100 pump control unit is designed for control and supervision of submersible pumps. Pump operation is automated without the use of floats or level sensors. The moment the pump begins to "snore" (i.e. pump air instead of liquid), the pump cycle is halted. The pump controller continually calculates an appropriate "off-time" and restarts the pump after the established time delay. By optimizing the pump cycle, both pump wear and power consumption will be reduced.

Download the datasheet (PDF)

For Resellers and High Volume Orders:
Please request a quote to obtain preferred pricing.

Features

  • Display indication
  • High level switch can be used to trigger start
  • Software controlled settings via a keypad
  • Supervision functions
  • Two relay outputs (PUMP and ALARM)

Specifications

    General
  • Alarm relay: 5 A, 240 VAC resistive. 1.5 A 240 VAC pilot duty / AC12
  • Compliance: CE and cUL
  • Current input: Current transformers; 10/0.055A; 25/0.055A; 50/0.055A; 100/0.055A; If current > 100 A, a 10A transformer is used with an outer standard transformer
  • Dimension (W×H×D): 45 × 90 × 115 mm (1.77” × 3.54” × 4.53”)
  • Electrical safety: IEC 947-5-1:1990 + A1:1994
  • EMC: EN50081-1, EN50082-2
  • Frequency: 45–65 Hz
  • Fuse: Max 10 A
  • Operating temperature range: –20 °C to 50 °C
  • Power Consumption: Max 6 VA
  • Protection Class: IP20
  • Pump relay: 5 A, 240 VAC resistive. 1.5 A 240 VAC pilot duty / AC12
  • Repeatability power measurement: ±1 unit in window 04, 24 h, 20 °C
  • Storage Temperature Range: –30 °C to 80 °C
  • Supply voltage (VAC): 3 × 100–240; 3 × 380–500; 3 × 525–690. Note! UL recognized only up to 600 V
  • Temperature tolerance: < 0.1 % in window 04 / °C
  • Terminal 3, for a closing contact: Internal supply 15–30VDC Short circuit current 10–20mA
  • Terminal 5, temperature input: Internal supply 15-30VDC Short-circuit current 2–2.5mA
  • Terminal wire size: Use 75 °C copper (Cu) wire only 0.2–4 mm2 single core, 0.2–2.5 mm2 flexible core, stripped length 8 mm
  • Weight: 0.3 kg (10.5 oz)

 

Applications

  • None Available

Aliases

  • None Available